P RESSURE  T RANSMITTER  PASCAL CV    T YPE  S ERIES FOR  FOOD /PHARMACEUTICALS /
CV 3110
BIOTECHNOLOGY
Signal output::
●  4..20 mA, can be retrofitted with optional HART ®
protocol ●PROFIBUS PA ■Function modules
●Multifunctional display with 5-segment digital display and bar graph
●HART ®
protocol
●Switching module with 2 floating channels, maximum 1.5 A
switching current, electrically isolated at all sides, without additional auxiliary power ■Function module replacement on site without recalibration "plug and measure"■Watchdog for electronics modules and measuring cell
■Hygienic design according to EHEDG, FDA und GMP recommendations ■Material and surface quality according to the hygienic requirements ■Limits of measuring 80 mbar 40 bar ■Accuracy: < 0.25% (linearity, hysteresis and repeatability)■Turndown 5:1
■Explosion protection: II 1/2G EEx ia IIC T6■Medium temperature  up to 160 °C
Piezoresistive measuring cell, directly aerated, fully welded
The pressure transmitter PASCAL CV is suited for measuring the relative and absolute pressures of gases, vapors and liquids. The type series CV3110 has been developed to meet the stringent demands of food processing, pharmaceutical technology, and biotechnology. Special attention has been given to good surface quality. Thus, for instance, roughness values to Ra 0.4 µm can be guaranteed for wetted parts (for welds: Ra < 0.8µm) or the system can be electropolished as well.
The modular design of the pressure transmitter allows users to choose the best possible device for his specific operating requirements.
PASCAL CV is equipped with a variety of process connections and uses smart module technology for display, switching and communication purposes.These functional modules can be exchanged or extended with ease without having to remove the transmitter from the process.Other designs available
●PASCAL CV 3100 for general application
●PASCAL CV 3120 for chemical/petrochemical industry
Process connection: all standard screw-in, flange and inline connections
Basic module
PROFIBUS
Function modules
Display module
HART ®-module
Switching
module
<20 mA
Data Sheet: D4-017/2
P. 1
Rev. 0D3
Housing hygienic housing design with screw cap and window
Material
housing:stainless 1.4301window:Macrolon gasket:NBR O-ring
Construction
two-chamber system, minimum housing volume, excellent moisture and condensate protection Pressure compensation PTFE filter system Degree of protection EN 60529, IP 66
replaceable
Climatic category DIN EN 60721 3-4, 4K4H
Electrical connection
· screwed terminals 1 mm², cable entry fitting through screwing
· circular plug connector M 12
Weight
standard device without diaphragm seal and function modules approx. 0.65 kg
Housing design
Construction welded design
Diaphragm modifications see page 5 or order code Material
stainless steel mat.-no. 1.4404 or 1.4435see order code
Sensor piezoresistive measuring element System fill
foodstuff oil FD1 (USDA-H1)according to FDA
Ambient temperature -20 to 85°C Process temperature depending on design Allowed storage temperature -40...85 °C
Note safety values as per examination certificate!Standard 40 VDC Ex-proof design
<30 VDC
Interference emission EN 50081 section 1Noise immunity
EN 50082 section 2EU examination certificate
II 1/2G EEx ia IIC T6
Data Sheet: D4-017/2
Housing design Measuring system Signal
<20 mA, two-wire,
optional with HART protocol (not yet available)
Current range    3.8 - 20.8 mA Current limitation approx. 22 mA Alarm state < 3.6 mA, optional > 21 mA Delay time approx. 160 ms measuring cycle    6 measurements / second Measuring range setting turndown 5:1Damping t 0.0 - 120.0 seconds
Load
R <(Ohm)
Limit point setting DIN 16086
Reference conditions DIN EN 60770-1
Calibration position vertical mounting position Linearity errors
< 0.15% of span TD 5:1 no change
Hysteresis < 0.05% of nominal range Repeatability < 0.05% of nominal range Influence of mounting position < 3.5 mbar Long-term drift < 0.1%/year of nominal range DIN EN 60770-1Temperature effect
a)Lower range value / upper range value in 60°C ± 0.15%/10 K of nominal range in range < 0°C, > 60°C ± 0.2%/10 K of nominal range b) process connection (diaphragm seal) depending on design flat diaphragm zero point error DN 25/1"4,8 mbar/10 K DN 32/1 1/2"2,3 mbar/10 K DN 401,6 mbar/10 K DN 50/2"0,6 mbar/10 K inline diaphragm zero point error DN 25/1"9,5 mbar/10 K DN 32/1 1/2"4,1 mbar/10 K DN 403,9 mbar/10 K DN 50/2"3,9 mbar/10 K
The specified zero error for the process connection is a guide value for a standard design. We can provide a detailed system calculation upon request. Systems with reduced diaphragm seal errors are also available.
Temperature ranges Output
Accuracy
Approval/tests
P 0    t  2xt  3xt 4xt  5xt
< damping t = 10 s = 50 s ~100 %
windows
O-ring-seal electronics
fully encapsulated replaceable
gasket
sensor chamber fully encapsulated (reduced volume)
plug connection cable entry fitting U - 12 V 22.5 mA
^Process connection separate terminal compartment (reduced volume)
terminals
pressure sensor with direct connection to atmospheric
pressure compensation
atmospheric pressure
compensation
P. 2
100 %63 %
Supply limits of measuring range meas. span nominal range: e.g. 1 bar
Data Sheet: D4-017/2
Display module (multifunctional display) optional
·Module housing made of ABS, encapsulated electronics unit
·Many operating mode menus ·5-segment pressure read-out with unit ·Read-out display
-pressure (standard)-percent -current
-sensor temperature
·Bar graph 36 segments = 0...100%
·Measuring circuit test (current sensing function)22.0 mA
·Alarm indicator on display
·Switching function indicator (with switching module)
Switching module, optional
·No additional auxiliary power required ·Module housing made of ABS, encapsulated electronics unit ·
  2 limit values, voltage free, short-circuit-proof ·Switching capacity 50 V DC / 500 mA (Ri < 1.5 Ω)or 30 V DC / 1.5 A (Ri < 0.3 Ω)·Overload indicator: LED red, overload or short-circuit ·Fusible cut-out at overload /short-circuit with automatic reset ·Switch points: 0.0 - 100.0% adjustable Standard: 50.0%
·Switching function: maker or breaker, adjustable Standard: breaker ·Device off circuit: contact open ·Hysteresis: 0.0% to 100.0%, adjustable standard: 0.1%
falling or rising, adjustable,standard: falling ·Switching rate: 6 Hz
·Electrically isolated to all sides
Insulation voltage: 500 V, 2.5 kV/2 sec.·Electrical connection: terminal blocks 1 mm²
pluggable with automatic module detection - plug and measure -
P. 3Profibus module description and HART ® connection upon request ^
pluggable with automatic module detection - plug and measure -
Basic module: 4...20 mA
Data Sheet: D4-017/2
Switching module
x  = configurable w = factory setting
P. 4
Data Sheet: D4-017/2
Mounting position
Housing
Process connections
P. 5
(short term up to 140°C, 1h)