B-I Fire Detection System
MODEL: BDS-4000
Ver. 1.0
Software Procedure
generatedB-I INDUSTRIAL CO., LTD.
Web site : www. kr , E-mail : kr
▣ SEOUL HEAD OFFICE ▣ BUSAN FACTORY
Ace Hightech City 1-618, 55-20 Munrae-dong3 2508-1, Daejeo-2dong, Kangseo-gu, Yeongdeungpo-gu, Seoul, Korea Busan, Korea
Tel: 02) 706-3077 Tel: 051) 441-5670
Fax: 02) 702-3076 Fax: 051) 441-6225
Index
◈ MAIN PANEL
1. Operation menu
1.1. Start ---------------------------------------------------------- 3 1.
2. Fault ---------------------------------------------------------- 4 1.
3. Fire pre-alarm ------------------------------------------------- 5 1.
4. Fire alarm ----------------------------------------------------- 7
2. Menu construction
2.1. Menu flowchart ----------------------------------------------- 8 2.2. Menu information --------------------------------------------- 9
1. VIEW ALARMS LIST ---------------------------------------------- 10
2. DISABLEMENT -------------------------------------------------- 11
3. SYSTEM CHECK ------------------------------------------------ 14
4. SYSTEM SETTING ----------------------------------------------- 17
5. SYSTEM CONFIGRATION ----------------------------------------- 18
◈ REPEATER PANEL
1. Operation menu
1.1. Start --------------------------------------------------------- 27 1.
2. Alarm -------------------------------------------------------- 27
2. Menu construction
2.1. Menu flowchart ---------------------------------------------- 28 2.2. Menu information -------------------------------------------- 28
1. VIEW ALARMS LIST ---------------------------------------------- 29
2. KEY &LED TEST ------------------------------------------------- 30
3. SET TIME ------------------------------------------------------ 30
4. UPGRADE FROM USB -------------------------------------------- 30
◈ MAIN PANEL
1. Operation menu
1.1. Start
* Loop display can be indicated up to 12 loops, the maximum loop number of BDS-4000 SYSTEM. And the loops set up as “ABLE” before being reset will be progressing.
* Every device connected with the pertinent loop is checked.
* Progress state is displayed as % through setting standards that maximum 127 detectors per loop can be loaded
* In case that setting state after system reset is different from the setting state set up before, device f
ault will occur.
* NORMAL HOME MENU 상태
1.2. Fault
FAULT TYPE: LOOPS FAULT, DEVICE FAULT, UNEXPECT DEVICE FAULT, MAIN POWER FAULT, EMERGENCY POWER FAULT, BATTERY FAULT, EARTH FAULT EXTERNAL
SOUNDER FAULT, DOOR HOLDER1,2 FAULT, COMMUNICATION FAULT:
REPEATER, INTERFACE, EXTERNAL RELAY BOARD, LOOP CARD
FAULT PROCESS: In case system fault LED flickers, buzzer beeps and the external output is on, please push Mute KEY repeatedly which can make buzzer beep or not beep
and touch ACK which can make HOMM MODE(FAULT ALARM MODE)
converted and LIST & RESET windows related to generated fault will be
activated. However, in case of communication fault occurs, COMM ALARM
LED will flicker
* LOOP FAULT EXAMPLE
☞ LIST : can make you check generated alarm lists.
☞ RESET : can make you reset generated alarm.
But reset will be processed after the input of ACCESS LEVEL2 SECURITY NUMBER.
1.3. FIRE PRE-ALARM
PRE-ALARM PROCESS: In case system fault LED flickers, buzzer beeps and the external output is on, please push Mute KEY repeatedly which can make buzzer beep or not beep
and touch ACK which can make HOMM MODE(FAULT ALARM MODE) converted
and LIST & RESET windows related to generated pre-alarm will be activated.
* FIRE PRE-ALARM EXAMPLE
* Analogue value transmitted by devices is indicated real time ( Refer to page 48)