I N S TA LL ATI O N M A N UA L
Stanilite®
Exit LED jumbo
Standard, Nexus® LX, Nexus RF
Doc no. 29-99575_2
This document covers What’s inside the box
Safety warning
Exit LED jumbo Installation instructions Installation manual Removal instructions Warranty information
Testing precautions Troubleshooting guide
Testing precautions
Once the fitting is permanently connected to the mains supply, a commissioning discharge test as required in AS/NZS 2293.2 must be carried out. You will need to allow 24 hours for the battery to fully charge prior to conducting this test,
presently (at the time of writing), the standard requires that fittings operate in emergency mode for a period not less than 2 hours for their commissioning test and for not less than 90 minutes thereafter (it is required that 6 monthly discharge tests be carried out). You will need to keep the records for the commissioning test and enter them into the building emergency services logbook or via other recording methods as allowed by AS/NZS 2293.2.
Troubleshooting guide
If you have installed and connected the fitting as per the instructions listed earlier and it does not function correctly, use the following table as a guide to fixing the problem. Look up the type of fault in the left column and check the possible causes from the right column.  If the fitting still does not work after checking these possible causes, contact ABB customer service in Australia on 1800 60 20 20.
ABB Australia Pty Limited For enquiries
ABB contact centre: 1800 60 20 20E-mail:************************
www.stanilite.au
service fault© Copyright 2019 ABB. All rights reserved.
9A K K 106930A 9795 - A  - J u l  2019
Construction sites
Continuously switching off the mains power supply that is connected to emergency light fittings during the construction phase of an
installation will cause these fittings to discharge and charge their batteries many times over a short period; this can shorten life of the battery. ABB does not recommend such practices and may not honour the warranty on batteries when they are subjected to such harsh operating
conditions. Emergency light fittings are designed to be discharge tested once every 6 months as per
AS/NZS 2293.2, subjecting the product to repeated discharge or charge cycles is regarded as an abuse of the fittings.
Thank you for choosing ABB product
Please read this document thoroughly before commencing installation and retain for future reference. Contact ABB customer service in Australia on 1800 60 20 20 if you need any assistance. The installation instructions were correct at the time of print. To reflect changes in technology and Australian standards; ABB reserves the right to amend the instructions
without notice. Updated document can be found on the Stanilite website.
Safety warning
In Australia and New Zealand, only licensed electricians are permitted by law to work with 240 volt electrical installations.
Do not attempt to install or connect this product unless you are a licensed electrician.
Turn off and isolate the electrical supply before connecting this fitting to the building wires.Do not touch the terminals of the terminal block when the light fitting is energised.
The only user-serviceable part is the battery pack. LED light source is not user-serviceable.Do not attempt to service other parts of the fitting as this will void the warranty.
As the installer, it is your responsibility to ensure compliance with all relevant building and safety codes, (ie: AS/NZS 3000, AS/NZS 2293). Refer to
Important to note:
• This product is designed for indoor use only.the applicable standards for data and mains cabling installation procedures and requirements.
Nexus LX (data cable system)
The Nexus range of emergency light fittings are designed to be connected together into a special communication network over a level 4 (or higher) high speed, single twisted pair data cable. The Nexus user and technical guide describes all you need to know to successfully install a Nexus project. Ask for it from your superviser, from your employer or from your nearest ABB product supplier. The network cabling of the building must be installed as per the procedure detailed in the Nexus user and technical guide. No mains or mains carrying cables are to be connected to the data terminals or cables.Nexus RF (wireless system)
The Nexus RF range of light fittings are designed to communicate via a proprietary RF network, however the electrical installation of the fittings is identical to that of a standard non-monitored fitting.
No.Fitting
type Fault
Possible causes
1
Standard Nexus LX Nexus RF LEDs do not light up when connected to mains
AC supply not connected or turned off; or Switch active turned off; or LEDs damaged
2
Nexus LX
Indicator LED is flashing green but AC lamp does not come on when connected to mains Switch active turned off; or Lamp damaged; or
Missing loop from unswitched to switched active 3Nexus LX
Indicator LED is flashing green but lamp does not come on when test switch is pressed
Switch active turned off; or LEDs damaged; or
Battery pack not connected or faulty; or Test switch damaged
4Nexus LX Indicator LED does not light up red after the commissioning
Battery pack not connected; or
LED wire not properly inserted into the terminal 5
Standard Nexus LX Nexus RF LEDs are lit momentarily when test switch is pressed or when mains fail Battery not fully charged (allow up to 24 hours); or Battery pack damaged
6Nexus LX Indicator LED is constant green
Fitting self checks fail - return to manufacturer 7
Nexus LX
Nexus RF
Fitting LED is not flashing yellow/orange under wink node command
Fitting is not receiving communication signal Check data cable wiring path and cable or RF connections
Refer to Nexus user and technical guide
Installation instructions
1. Unscrew 2 screws and remove 1 end panel. Slide and remove the diffuser from the base and then
remove the base cover/LED panel assembly (2 screws) and unplug the interconnecting cable.
Note: Do not touch the LEDs and ensure that the LED assembly is not damaged whilst it is removed from the product.
Fitting type Indicator LED state - on initial powering - no fitting faults
Non-monitored Solid red Nexus LX Flashing green
Nexus RF
Green flash with 2 red blinks, green flash with 3 red blinks
Removal instructions
1. Before uninstalling, de-energise and lock off
the mains supply to the fitting.
Warning: There may be 2 active supplies present, ensure both are de-energised .
2. Open one end plate, remove the diffuser and
base cover/LED panel assembly.
3. Unscrew the unswitched active, neutral and
earth cable connection from the terminal block.
4. For Nexus LX fitting; unplug the data cable
connection from the terminal. Disconnect the battery plug from the battery and unscrew the mounting screws of the gear tray. When the fitting is reconnected to the supply, it will need time to recharge its battery for 24 hours before it will be capable of a full length discharge again.
Fitting type/fitting state Normal operation
Test switch pressed (after few minutes charging)
Maintained - no SA LEDs will be on
LEDs will go into emergency mode Maintained - with SA
LEDs will follow the SA state
LEDs will go into emergency mode
Wire/fitting type Maintained - no SA
Maintained - with SA Switched active Loop the SA and A terminals
Wire to SA terminal Unswitched active Wire to terminal A Wire to terminal A
2. The fitting can be either ceiling or wall mounted. The wall mount version comes with 2 right angle
brackets. Check the fitting type and orient the base to suit the mounting and cable access position an
d use the base as a template to mark mounting screws’ locations for either the base or the mounting brackets.
3. Cable entry is either via the cable entry hole in the rear of the base, knockouts in either end or cable
access hole/s can be drilled in the base to suit.
4. Secure the base to the ceiling or to the wall via the brackets supplied using appropriate fixings
(fixings not supplied due to the wide variety of building construction materials). 5. Run mains cable as appropriate through the base access hole.
6. Strip 9mm insulation length from mains cable, connect and terminate wires to the terminal block. Be
careful with multi-strand conductors that all the strands are twisted together before insertion into the terminal. Any stray strands that inadvertently come into contact with their neighbouring terminal will cause undesirable results when the fitting is powered.
7. Verify that the battery is connected to the power pack. Fit test switch and LED charge indicator to
the holes provided in the side of the base.
8. Refit the base cover/LED panel assembly by reversing the instructions in point 1. Energise the fitting,
allow a few minutes charging time and then check the operation in accordance with the table below. Refer to the troubleshooting guide at the end of this document if abnormal operation or indication is encounted.
9. Refer to the Nexus user and technical guide for detailed description of all possible LED patterns and
their meanings.
10. Fit the diffuser and secure the end plate to the base.
Antenna
Cable
Important: 24 hours is required to allow the fitting battery to reach full capacity, ie: prior to a discharge test. As the installer, it is your responsibility to conduct the initial discharge testing of the installed fitting. Refer to AS/NZS 2293.

版权声明:本站内容均来自互联网,仅供演示用,请勿用于商业和其他非法用途。如果侵犯了您的权益请与我们联系QQ:729038198,我们将在24小时内删除。